Vacuum Circuit Breaker (VCB)
Application
Indoor / Outdoor Vacuum Circuit Breaker panel used to Control and protection of the power supply to motors, transformers, capacitors and other feeder circuits. Designed for indoor / outdoor use and is particularly suitable for
Electric power plants
Substations
Industrial plants
Commercial buildings
Pumping stations
Pipeline stations and
Transportation systems.
Large infrastructures: Airports, railways, etc.
Installation in AIS cubicles
Power stations: Wind farms
Utilities: Primary distribution substations
Industry: Chemical, Iron and steel, automobile, etc.
VCBs are available at rated voltages of 6.6 to 36 kV, with rated short-circuit breaking capacities from 25 to 40 kA.
SALIENT FEATURES
HIGH RELIABILITY:
Testing is performed by an independent testing team. Fully Insulated Design and all the operations are behind the closed doors. All components, such as current transformers, voltage transformers and multifunction relays are made of the highest quality materials. Our new generation design has reduced the number of parts, which reduces the chance of failure.
SAFETY:
Compartment partitions and an automatic shutter system completely isolate live parts. Comprehensive interlocking mechanisms are used for Safe Operations. MAX VCBs are designed to withstand the huge pressure and burning effect of the arc to withstand in the event of an internal arc fault.
HIGH PROTECTION:
Specially designed Multiple Protection Relays are installed to provide protection, measurement, and communications and control functionality.
FLEXIBLE DESIGN FOR EASY INSTALLATION:
Flexible features like readily extensible, Panels with main circuit and control cable entry from either the top or bottom are available for easy installation. Installation and testing duration are considerably reduced as the panel is tested in the factory and then delivered as a complete unit.
STANDARD TECHNICAL FEATURES OF MAX SERIES CIRCUIT BREAKER PANELS | ||||||
TYPE | VMAX6 | VMAX7 | VMAX12 | VMAX17 | VMAX24 | VMAX36 |
Rated Voltage (kV) | 6.6 | 7.2 | 12 | 17.5 | 24 | 36 |
Frequency (Hz) | 50 | 50 | 50 | 50 | 50 | 50 |
Rated Insulation level (1 min) kV rms | 20 | 20 | 28/36 | 36 | 50 | 70 |
1.2/50 micro sec. impulse (kV peak) | 60 | 60 | 75/95 | 95 | 125 | 170 |
Rated Current A | 630/1250/2000 | 630/1250/2000 | 630/1250/2000 | 630/1250/2000 | 630/1250/2000 | 630/1250/2000 |
Rated short time current rating (3 Sec) | 16/25/31.5 | 16/25/31.5 | 25/31.5/40 | 16/25/31.5 | 16/25/31.5 | 16/25/31.5 |
Rated short circuit breaking current (kA) | 16/25/31.5 | 16/25/31.5 | 25/31.5/40 | 16/25/31.5 | 16/25/31.5 | 16/25/31.5 |
Rated short circuit making current (kA) | 40/63/80 | 40/63/80 | 63/80/100 | 40/63/80 | 40/63/80 | 40/63/80 |
Operating Duty | 0-3 min-co-3 min-co | 0-3 min-co-3 min-co | 0-3 min-co-3 min-co | 0-3 min-co-3 min-co | 0-3 min-co-3 min-co | 0-3 min-co-3 min-co |
Operating time | < 70ms | < 70ms | < 70ms | < 70ms | < 70ms | < 70ms |
Operating Cycles | < 2 Cycles | < 2 Cycles | < 2 Cycles | < 2 Cycles | < 2 Cycles | < 2 Cycles |
Note: The standard specifications vary from time to time as our products undergo continuous developments |